Skip to main content
Fluid Controls

Product

PTM 2

Isolation and vent valves opposed across the block, with the drain taken on the process side.

A manifold

PTM 2

Two valve manifold is designed in a single block with female screwed inlet and outlet port combining isolation valve and vent / calibration valve. Generally used on static pressure transmitters, switches or gauges.

PTM 2 sets the isolation and vent valves opposite one another across the block and takes the drain on the process side. Process and instrument connections are 1/2" NPT (F) and the drain / vent is 1/4" NPT (F).

A drain plug is available as an option, as is a three piece union for positioning the gauge. Mounting bolts to IS 1364-1960 are supplied with the manifold.

Max working pressure
up to 620 kg/cm² body / 413 kg/cm² seat (hydrostatic test)
Body materials
A 105, A 182 / A 479 Gr F 304SS, A 182 / A 479 Gr F 316SS, Monel, Hastelloy
Thread systems
NPT
Heat-code traceable · 100% tested

Features

  • Isolation and vent valves opposed
  • Drain on the process side
  • Process 1/2" NPT (F), instrument 1/2" NPT (F)
  • Drain / vent 1/4" NPT (F)
  • Option: drain plug, three piece union for gauge positioning

Applications

  • Static pressure transmitter hook-ups
  • Pressure switch isolation
  • Gauge isolation and calibration
Max working pressure
up to 620 kg/cm² body / 413 kg/cm² seat (hydrostatic test)
Thread systems
NPT
Body materials
A 105, A 182 / A 479 Gr F 304SS, A 182 / A 479 Gr F 316SS, Monel, Hastelloy
Temperature
PTFE gland packing as standard; Graphoil above 180 °C
Testing
Hydrostatic body 620 kg/cm², seat 413 kg/cm²; pneumatic seat 40 kg/cm², at 25 °C